GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 265

Advertising
background image

Alarms and events description and system troubleshooting guide

265

A

Caution CPU Not Rcv From
Messngr

The CPU is not receiving data from a
Messenger

Check Ethernet connection between the
Entellisys Messenger and switch, and the
connection between the switch and CPU.
Verify that Messenger is powered on and
operating.

CPU Receiving From Messngr

The CPU is receiving data from a Messenger

Attention Discrete IO Error Flex
Logic Disabled

Number of discrete I/O cards detected by
CPU does not match number that it has been
programmed to expect

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Memory CRC Error
Replace CPU

CRC error has been detected in the CPU
memory, CPU should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

CPUA Assumes Control Logic

CPUA is running the control scheme

CPUA Relinquishes Control Logic CPUA is no longer running the control

scheme

CPUB Assumes Control Logic

CPUB is running the control scheme

CPUB Relinquishes Control Logic CPUB is no longer running the control

scheme

Attention Duplicate CPU IDs
Found

Both CPUs have the same ID

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note CPU Internal Error 1

CPU detected an internal error

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note CPU Internal Error 2

CPU detected an internal error

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note CPU Internal Error 4

CPU detected an internal error

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips

Advertising