8.3.3 User settings for Zone Selective Interlock

A ZSI zone is made of one or more MSGF zones, and main, tie, and feeder circuit breakers. A ZSI
zone can be either a ZSI-Short Time zone, ZSI-Ground Fault zone or both.

ZSI-Short Time zone

Members limited to main, tie, and feeder circuit breakers.

All main and tie circuit breakers should be assigned a tier number of 0 for Topology 0.

ZSI-Ground Fault zone

Members can be MSGF zones, and main, tie, and feeder circuit breakers.

All MSGF zones, and main and tie circuit breakers should be assigned a tier number of 0 for
Topology 0 (see Figure 8-7).

Figure 8-7 Reduced Energy Let-Thru Mode settings for Zone Selective Interlock