Alarms and events

254

A

Invalid MSGF Sum Zone1…2
Pkup Min Used

Pickup setting for multi source ground fault
for summation zone 1…2 has been set to the
minimum allowable (current setting is too
low)

Check pickup setting for MSGF Summation
zone. Value can be set higher if desired.

Invalid MSGF Sum Zone1…2
Alrm Pkup Min Used

Pickup setting 1 for alarm only multi source
ground fault for summation zone 1…2 has
been set to the minimum allowable (current
setting is too low)

Check pickup setting for MSGF Summation
zone. Value can be set higher if desired.

Relays – High Resistance GF

Pickup High Resistance GF

High resistance ground fault has entered
pickup

Dropout High Resistance GF

High resistance ground fault has dropped out
of pickup

Alarm High Resistance GF

High resistance ground fault alarm has
operated

Invalid Settings HRGF Unable To
Detect Phase

The product of the pickup current setting and
the ground resistance setting is greater than
the nominal phase voltage

Check pickup current and ground resistance
settings.

Relays – High Resistance GF Location

HRGF Location - Fault Located
Function 1-4

Logged when location function 1 located
fault at a breaker. Each breaker that location
function locates fault at will have a separate
event logged.

HRGF Location - Automatic
Mode Started Function 1-4

Logged when location function 1 is started
locating the fault in automatic mode.

HRGF Location - Automatic
Mode Ended Function 1-4

Logged when automatic mode finishes
regardless of the location results for location
function 1

HRGF Location - Manual Mode
Started Function 1-4

Logged when location function 1 is started
locating the fault in manual mode.

HRGF Location - Manual Mode
Stopped Function 1-4

Logged when manual mode location is
interrupted by user regardless of the location
results for location function 1

Alarm HRGF Location Function Logged when location function 1 activates

HRGF Location Trip Function 1-4
Could Not Issue Trip

Logged when HRGF Location could not issue
a trip command.

HRGF Location Trip Function 1-4
In Pick Up

Logged when HRGF Location is in pick up

HRGF Location Trip Function 1-4
Drop Out

Logged when HRGF Location is in drop out

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips