Synch Check relay

97

5

Live Bus Threshold: Adjust the threshold above which a phase is considered live from 50% to
100% of the nominal voltage (i.e., the PT rating, line-neutral for wyes, line-line for deltas) in steps
of 1% from the Live Bus Threshold drop-down menu in the Source 1 menu group.

5.3.2.4 Source 2

Dead Bus Threshold: Adjust the threshold below which a phase is considered dead from 5 to
50% of the nominal voltage (line-neutral for wyes, line-line for deltas) in steps of 1% from the
Dead Bus Threshold drop-down menu in the Source 2 menu group.

Live Bus Threshold: Adjust the threshold above which a phase is considered live from 50% to
100% of the nominal voltage (i.e., the PT rating, line-neutral for wyes, line-line for deltas) in steps
of 1% from the Live Bus Threshold drop-down menu in the Source 2menu group.

5.3.2.5 Configuration

Select the condition under which the “Dead Source” status output is true from the following
options in the Configuration drop-down menu:

None – Dead source function is disabled

LV1 and DV2 – Voltage source 1 live and voltage source 2 dead

DV1 and LV2 – Voltage source 1 dead and voltage source 2 live

DV1 or DV2 – Voltage source 1 dead or voltage source 2 dead

DV1 xor DV2 – One voltage source is dead, the other is live

DV1 and DV2 – Both sources are dead

NOTE: A source is considered dead when all voltage phases are below the dead bus threshold.
A source is considered live when all voltage phases are above the live bus threshold.

Figure 5-16 Settings for Synch Check Relay