Single point functions

78

5

Figure 5-7 Settings for Under Frequency Relay

5.2.4.5 Usage

Event logging
While the relay is functional, the following events are logged for the under frequency relay in the
Entellisys CPU:

Alarm Pickup Under Frequency – Alarm only under frequency relay has entered pickup.

Alarm Under Frequency – Alarm only under frequency relay has operated.

Alarm Dropout Under Frequency – Alarm only under frequency relay has dropped out of
pickup.

Voltage Below Underfreq Alarm Blocking Voltage – The voltage has dropped below the alarm
only under frequency blocking voltage threshold.

Voltage Above Underfreq Alarm Blocking Voltage – The voltage has exceeded the alarm only
under frequency blocking voltage threshold.

Pickup Under Frequency – Under frequency relay has entered pickup.

Breaker Trip Under Frequency – Under frequency relay has operated.

Dropout Under Frequency – Under frequency relay has dropped out of pickup.

Voltage Below Under Frequency Blocking Voltage – The voltage has dropped below the
under frequency blocking voltage threshold.

Voltage Above Under Frequency Blocking Voltage – The voltage has exceeded the under
frequency blocking voltage threshold.

To view these events, click Sequence of Events on the Main Menu.