Single point functions

90

5

5.2.9.2 Accuracy

The location relay is dependant on the CT size and differential current between the pulsing
contactor’s on and off state. The minimum differential pulse current will, in turn, depend on fault
impedance and the size of the grounding resistors.

Table 5-8 CT accuracy in terms of detectable fault currents

CT Rating (Amps)

Minimum detectable

differential current

(Differential amps)

150

1.0

400

1.0

800

1.0

1,600

1.0

2,000

1.2

3,200

1.5

4,000

2.0

5,000

3.0