Introduction to FlexLogic

179

11

Logic Gate

NOT

Logic Not

Operates on the previous
parameter.

OR (2)

OR (16)

2 input OR gate

16 input OR gate

Operates on the 2 previous
parameters.

Operates on the 16
previous parameters.

AND (2)

AND (16)

2 input AND gate

16 input AND gate

Operates on the 2 previous
parameters.

Operates on the 16
previous parameters.

NOR (2)

NOR (16)

2 input NOR gate

16 input NOR gate

Operates on the 2 previous
parameters.

Operates on the 16
previous parameters.

NAND (2)

NAND (16)

2 input NAND gate

16 input NAND gate

Operates on the 2 previous
parameters.

Operates on the 16
previous parameters.

XOR (2)

2 input Exclusive OR gate

Operates on the 2 previous
parameters.

LATCH (S, R)

Latch (Set, Reset) - reset-dominant

The parameter preceding
LATCH (S, R) is the Reset
input. The parameter
preceding the Reset input is
the Set input. 512 available

Timer

TIMER 1

TIMER 160

Timer set with FlexLogic Timer 1 setting.

Timer set with FlexLogic Timer 160
settings.

The timer is started by the
preceding parameter. The
output of the timer is TIMER
#.

Assign Virtual
Output

= Virtual Output 1

= Virtual Output
480

Assigns previous FlexLogic parameter to
Virtual Output 1.

Assigns previous FlexLogic parameter to
Virtual Output 480.

The virtual output is set by
the preceding parameter.

Table 11-3 FlexLogic operators

Type

Syntax

Descriptions

Notes