GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 189

Advertising
background image

FlexLogic example

189

11

[87] Virt Op 2 On
[88] Virt Ip 1 On
[89] DIG ELEM 1 PKP
[90] XOR (2)
[91] Virt Op 3 On
[92] OR (4)
[93] LATCH (S, R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR (3)
[98] TIMER 2
[99] = Virt Op 4

c. It is now possible to check that the selection of parameters will produce the required

logic by converting the set of parameters into a logic diagram. The result of this process
is shown below in Figure 11-7 and can be compared to the “Logic for Virtual Output 4”
diagram (Figure 11-4) as a check.

Figure 11-7 FlexLogic equation for Virtual Output 4