Alarms and events description and system troubleshooting guide

255

A

HRGF Location - Breaker Trip

Logged when location function 1 trips

HRGF Location - Discrete Output
Unavail Function 1-4

Logged when one of the following conditions
takes place
- no discrete I/O card in the system, wrongly
configured or hardware failure
- no discrete outputs are configured
- none of the configured outputs is set to be
operated by HRGF Location function 1

HRGF Location - Detection Not
Optioned Function 1-4

Logged when breaker that location function
1 is associated with does not have HRGF
optioned.

FlexLogic Ended Reduced
Let-Thru Mode-Multipoint

Logged when FlexLogic disables multipoint
RELT

HRGF Location Incomplete
Missing Data Function 1-4

This event is logged when some messengers
are either decommissioned or
non-communicating or not-synched.

Relays – Synch Check

Synch Check Control Enabled
1…12

Synch check relay 1…12 has been enabled

Synch Check Control Disabled
1…12

Synch check relay 1…12 has been disabled

Synch Check 1…12 Sources Not
Synchronized

Messengers that are providing voltage
information for synch check relay are not
synchronized, so the CPU is unable to check
for synchronization between voltage sources.

This should only happen on start-up, or when
a Messenger is connected to the system (or
rebooted). If it happens repeatedly during
normal operation, contact GE Post Sales
Service (see

How to contact us on page 2

).

Synch Check 1…12 Sources Not
Compatible

Voltage sources for synch check relay 1…12
are not compatible; i.e., they have different PT
configurations or ratings

Verify that the Source Voltages for the
synch check relay are correct.

Verify that the source voltages have the
correct PT configurations.

Synch Check 1…12 Dead Source
Operate

Dead source criteria for synch check relay
1…12 have been met

Synch Check 1…12 Dead Source
Drop Out

Dead source criteria for synch check relay
1…12 have been met

Synch Check 1…12 V1 Above
Minimum

Voltage source 1 for synch check relay 1…12
is above the live source threshold

Synch Check 1…12 V1 Below
Maximum

Voltage source 1 for synch check relay 1…12
is below the dead source threshold

Synch Check 1…12 V2 Above
Minimum

Voltage source 2 for synch check relay 1…12
is above the live source threshold

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips