GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 171

Advertising
background image

Introduction to FlexLogic

171

11

Table 11-2 describes all available operands available for all entellisys relays and are listed
alphabetically by operand type.

NOTE: While all relay elements and operands are available in FlexLogic, relays that are
optionable will not function unless properly optioned and configured.

Table 11-2 Entellisys FlexLogic operands

OPERAND TYPE

OPERAND SYNTAX

OPERAND DESCRIPTION

ELEMENT:
Breaker Control

BREAKER 1 OPENED
BREAKER 1 CLOSED
BREAKER 1 LOCKED OUT
BREAKER 1 CLOSED SPRING CHRGD
BREAKER 1 PRIMARY CONNECTED
BREAKER 1 PRIMARY DISCONNECTED
BREAKER 1 SECONDARY CONNECTED

Breaker 1 open
Breaker 1 closed
Breaker 1 locked out
Breaker 1 closing spring charged
Breaker 1 primary connected
Breaker 1 primary disconnected
Breaker 1 secondary connected

BREAKER 1 AVAILABLE

TRUE when both the primary and secondary
disconnects are connected.

BREAKER 1 READY

TRUE when the breaker is closed and both
primary and secondary are connected.

BREAKER 1 OPEN FAILED

TRUE when open operation failed for the
breaker. The result is set until breaker
opened. Applies to all open and trip
commands: shunt trip open, shunt trip, flux
shifter open, flux shifter trip.

BREAKER 1 CLOSE FAILED

TRUE when close operation failed for the
breaker. The result is set until breaker
closed.

BREAKER 1 FAULT

TRUE when LT, ST, GF, multipoint relays or
single point relays operated on a fault. The
result is set until the fault is cleared. Breaker
x Fault is returned to false when the breaker
is opened or open time-out (550ms).

BREAKER 2…30

Same set of operands as shown for
BREAKER 1