Single Point Relay protection

73

5

5.2.2.5 Usage

Event logging
The following events are logged for the Overvoltage relay in the Entellisys HMI:

Alarm Pickup Overvoltage – Alarm only overvoltage relay has entered pickup

Alarm Overvoltage – Alarm only overvoltage relay has operated

Alarm Dropout Overvoltage – Alarm only overvoltage relay has dropped out of pickup

Pickup Overvoltage – relay has entered pickup

Breaker Trip Overvoltage – relay has operated

Dropout Overvoltage – relay has dropped out of pickup

To view these events, click Sequence of Events on the Main Menu.

5.2.3 Over Frequency Relay

The Entellisys System executes the Over Frequency Relay function by comparing the
fundamental frequency of the phase A voltage to the programmed pickup set point.

The relay can be in three states:

Pickup – If the frequency of the phase A voltage is greater than the pickup set point, the
relay goes into pickup, and is said to enter Pickup state

Operate – If the relay stays in pickup state for a specified pickup delay time, the system trips
the appropriate circuit breaker or activates an alarm, and the relay is said to be in Operate
state

Drop out – The relay drops out of pickup when the frequency drops below 97% of the
programmed threshold. The relay is said to be in Drop out state.

The system trips the appropriate circuit breaker or activates an alarm if the frequency is greater
than the pickup set point for the specified time delay.

5.2.3.1 Accuracy

Pickup accuracy is less than

±

0.1 Hz. Trip time accuracy is

±

0.1 seconds.

Blocking voltage option: A 'blocking voltage' user-defined input option is provided. The over
frequency relay function is not performed if the blocking voltage option is enabled and the
voltage is less than the blocking voltage. If the Over Frequency Relay goes into pickup, and the
voltages subsequently drop below the blocking voltage, the relay goes out of pickup and the
delay is reset.