GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 256

Advertising
background image

Alarms and events

256

A

Synch Check 1…12 V2 Below
Maximum

Voltage source 2 for synch check relay 1…12
is below the dead source threshold

Overcurrent (including GF)

Pickup ST Overcurrent

Short time overcurrent function has entered
pickup

Dropout ST Overcurrent

Short time overcurrent function has dropped
out of pickup

Breaker Trip ST Overcurrent

Breaker tripped due to short time overcurrent
condition

Pickup LT Overcurrent

Long time overcurrent function has entered
pickup

Dropout LT Overcurrent

Long time overcurrent function has dropped
out of pickup

Breaker Trip LT Overcurrent

Breaker tripped due to long time overcurrent
condition

Pickup Ground Fault

Ground fault function has entered pickup

Dropout Ground Fault

Ground fault function has dropped out of
pickup

Breaker Trip Ground Fault

Breaker tripped due to ground fault condition

Alarm Ground Fault

Ground fault alarm has operated

Invalid Setting IOC Change
Rejected

Attempt to enable or disable IOC has been
rejected

The setting entered for IOC enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting IOC Pickup
Change Rejected

Attempt to change IOC pickup setting has
been rejected

The value entered for the IOC pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Invalid Setting GF Change
Rejected

Attempt to enable or disable ground fault has
been rejected

The setting entered for GF enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting GF Pickup
Change Rejected

Attempt to change the ground fault pickup
setting has been rejected

The value entered for the GF pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Table A-2 Sequence of events description and troubleshooting guide