3 relay settings – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 132
Advertising
Reduced Energy Let-Thru Mode
132
8
8.3 Relay Settings
Although the Topology 0 settings are user-adjustable, the values described in sections 8.3.1.
through 8.3.3 are an example of the highest level of protection.
Topology 0 settings, by default, are not enabled and will need to be adjusted by an
administrator before Reduced Energy Let-thru mode can be affective.
To change, Navigate to the Advanced Protection screen located on the (Main Menu, User
Settings)
NOTE: The system will only change settings when the multipoint relays are not in an
overcurrent condition.
Advertising