2 setup, 3 trip settings, 4 alarm settings – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 80

Advertising
background image

Single point functions

80

5

5.2.5.2 Setup

To set the Trip and Alarm settings for the Phase Loss relay
1.
On the Main Menu, click User Settings, and then select Relay Protection.
2. On the Relay Protection screen, choose the circuit breaker number from the drop-down

menu and click Phase Loss.

The remainder of this section discusses the relay parameters that can be set in the Phase Loss
section of the Relay Protection screen as shown in Figure 5-8.

5.2.5.3 Trip settings

Relay Enabled: Select Enabled to enable the relay.

Pickup: Adjust the phase loss pickup from 8% to 50% in increments of 1% from the Pickup
Setting
drop-down menu.

Delay: Adjust the phase loss delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage. If the option is enabled, the blocking voltage setting is 5% of the nominal
voltage.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.

5.2.5.4 Alarm settings

Relay Enabled: Select Enabled to enable the relay.

Pickup: Adjust the phase loss pickup from 8% to 50% in increments of 1% from the Pickup
Setting
drop-down menu.

Delay: Adjust the phase loss delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage. If the option is enabled, the blocking voltage setting is 5% of the nominal
voltage.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.