4 alarm settings – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 72

Advertising
background image

Single point functions

72

5

5.2.2.4 Alarm settings

Relay Enabled: Select Enabled to enable the relay.

Pickup: Adjust the overvoltage pickup from 105% to 125% in increments of 1% from the Pickup
Setting
drop-down menu.

Delay: Adjust the overvoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

Operate if any one phase is below the pickup threshold

Operate if any two phases are below the pickup threshold

Operate if all three phases are below the pickup threshold

Figure 5-5 Settings for Overvoltage Relay