Troubleshooting

53

4

4.8 Troubleshooting

Current reads zero or dashes

Verify that the Messenger is communicating to the CPU in the System Health screen. See

Monitoring system health on page 205

for more information.

Verify that the frame and CT ratings are properly configured. This information is available on
the Metering & Waveforms menu. See

Basic configuration on page 41

.

Verify the current exceeds 1% of CT rating. The system will zero the current if below 1%. To
verify this, trigger a waveform manually. The actual current will be displayed on the
waveform.

Voltage reads zero

Verify that the circuit breaker has a source for voltage data and that the source has a valid
PT assigned to it by clicking Metering on the Metering & Waveforms screen. See

Basic

configuration on page 41

. Also see

PT Throw-Over on page 115

for more information.

Detailed, Demand, or Advanced metering buttons are grayed out

Verify that the corresponding option has been assigned to that circuit breaker. See

Options

on page 43

.