GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 266

Advertising
background image

Alarms and events

266

A

CPU Updates (firmware & options)

CPU Firmware Download
Started

CPU firmware download process started

CPU Firmware Download
Complete

New firmware has been downloaded to CPU

Upgrade Successful

New option string successfully downloaded
to CPU

Upgrade Failure Internal Error 2 CPU detected an internal error during the

option upgrade process

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Internal Error 3 CPU detected an internal error during the

option upgrade process

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Internal Error 4 CPU detected an internal error during the

option upgrade process

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Option String
Corrupt

Invalid or corrupted option string: incorrect
option string format

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Unable To
Decrypt

Invalid or corrupted option string: decryption
failure or bad digital signature

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Due To Bad
CRC

Invalid or corrupted option string: bad CRC

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Upgrade Failure Hardware
Mismatch

Invalid or corrupted option string: MAC
address mismatch

Contact GE Post Sales Service (see

How to

contact us on page 2

).

CPU Firmware Failure Previous
Version In Use

CPU firmware upgrade operation failed; CPU
is using previous firmware version

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention New Messngr Options
Deficient

More per-breaker options are enabled then
the number available per the option string.
This can occur when a new option string is
loaded that contains fewer per-breaker
options than the original option string.

The CPU will allocate the options to the
lowest numbered breakers that have the
option specified. For metering options,
allocate the available meters to the desired
breakers. For relaying options, contact GE
Post Sales Service (see

How to contact us

on page 2

).

Preventative Maintenance

Breaker In Service Anniversary

Breaker anniversary date has been reached

Breaker Mechanical Life At XX
Percent

See section on Preventative Maintenance

Breaker Load Life At XX Percent See section on Preventative Maintenance

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips

Advertising