GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 247

Advertising
background image

Alarms and events description and system troubleshooting guide

247

A

Alarm Pickup Undervoltage

Alarm only undervoltage relay has entered
pickup

Alarm Undervoltage

Alarm only undervoltage relay has operated

Alarm Dropout Undervoltage

Alarm only undervoltage relay has dropped
out of pickup

Voltage Below Undervoltage
Alarm Blocking Voltage

The voltages on all three phases have
dropped below the alarm only undervoltage
blocking voltage threshold.

Voltage Above Undervoltage
Alarm Blocking Voltage

The voltage on at least one of the three
phases has exceeded the alarm only
undervoltage blocking voltage threshold.

Pickup Undervoltage

Undervoltage relay has entered pickup

Breaker Trip Undervoltage

Undervoltage relay has operated

Dropout Undervoltage

Undervoltage relay has dropped out of
pickup

Voltage Below Undervoltage
Blocking Voltage

The voltages on all three phases have
dropped below the undervoltage blocking
voltage threshold.

Voltage Above Undervoltage
Blocking Voltage

The voltage on at least one of the three
phases has exceeded the undervoltage
blocking voltage threshold.

Alarm Pickup Overvoltage

Alarm only overvoltage relay has entered
pickup

Alarm Overvoltage

Alarm only overvoltage relay has operated

Alarm Dropout Overvoltage

Alarm only overvoltage relay has dropped
out of pickup

Pickup Overvoltage

Overvoltage relay has entered pickup

Breaker Trip Overvoltage

Overvoltage relay has operated

Dropout Overvoltage

Overvoltage relay has dropped out of pickup

Alarm Pickup Phase Loss

Alarm only phase loss relay has entered
pickup

Alarm Phase Loss

Alarm only phase loss relay has operated

Alarm Dropout Phase Loss

Alarm only phase loss relay has dropped out
of pickup

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips