1 event logging – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 99

Advertising
background image

Synch Check relay

99

5

5.3.3.1 Event logging

The following events are logged for the Synch Check relay:

Synch Check Control Enabled 1…12 – Synch check relay 1…12 has been enabled

Synch Check Control Disabled 1…12 – Synch check relay 1…12 has been disabled

Synch Check 1…12 Sources Not Synchronized – Messengers that are providing voltage
information for synch check relay are not synchronized, so Entellisys is unable to check for
synchronization between voltage sources.

Synch Check 1…12 Sources Not Compatible – Voltage sources for synch check relay 1…12 are
not compatible; i.e. they have different PT configurations or ratings

Synch Check 1…12 Dead Source Operate – Dead source criteria for synch check relay 1…12
have been met

Synch Check 1…12 Dead Source Drop Out – Dead source criteria for synch check relay 1…12
have been met

Synch Check 1…12 V1 Above Minimum – Voltage source 1 for synch check relay 1…12 is
above the live source threshold

Synch Check 1…12 V1 Below Maximum – Voltage source 1 for synch check relay 1…12 is
below the dead source threshold

Synch Check 1…12 V2 Above Minimum – Voltage source 2 for synch check relay 1…12 is
above the live source threshold

Synch Check 1…12 V2 Below Maximum – Voltage source 2 for synch check relay 1…12 is
below the dead source threshold

To view these events, click Sequence of Events on the Main Menu.