Sequence of events, fault reports and waveform capture records

146

9

“Alarm Dropout High Current Trigger” - logged when current at the breaker goes below the
dropout level

“Alarm High Current Trigger” - logged when function operated (i.e. current stayed above
pickup level for the duration of the set time delay)

“HCTR Waveforms Max Count Reached” - logged when maximum set number of waveforms
has been triggered by the function

“HCTR Waveforms Counter Reset” - logged when user resets waveform count

Alarms

“High Current Trigger - Any”

“High Current Trigger - Breaker X” - where X stands for breaker number from 1 thru 30

9.3.1 Configuration

The High Current Trigger relay is associated to a specific breaker. From the User Setting
sub-menu, click on Relay Protection, select the appropriate breaker and click on the HC Trigger
button.

Figure 9-11 High Current Trigger Settings

Function settings are grouped into two groups. One is dedicated to the alarm settings and the
other group allows user to set waveform trigger limit.