3 setup – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 91

Advertising
background image

Single Point Relay protection

91

5

5.2.9.3 Setup

The HRGF Location functionality is an extension to the HRGF Detection relay. Since the location
process starts after a fault has been detected by HRGF Detection, the configuration parameters
specified for the HRGF Detection functionality must be set for the feature to work.
The High Resistance Detection and Location Relays are only available on breakers which have a
ground CT installed by the factory. To navigate to the setup screen login as an administrator to
the HMI and open the Advanced Protection (Main Menu, User Settings)

Figure 5-13 High Resistance GF Location settings

Select Breaker With Ground CT - Lists only breakers with ground CT’s assigned to them from
the factory

HRGF Location Function: Lists the available location relays - if optioned. Typically will reflect the
number of mains in the system equipped with HR equipment.

Detection Function: See

Setup on page 86

Location Relay Group box

Contactor Frequency: (0.5 - 2 Hz or 30 - 120 pulses per minute) Frequency at which the
contactor will pulse. User can adjust depending on the sensitivity of hand held amp meters
used to locate the fault downstream of Entellisys.