Alarms and events

246

A

Attention: CPU Firmware Version
Mismatch between CPUA and
CPUB

The firmware revisions are not consistent
between the primary and redundant CPUs.

Check the CPU Firmware tab under the
maintenance menu, or contact GE Post Sales
Service (see

How to contact us on page 2

).

Note that a sufficient privilege level is
required to perform this operation.

CPUA Commissioned

CPU A transitioned from the decommissioned
state to the commissioned state.

CPUB Commissioned

CPU B transitioned from the decommissioned
state to the commissioned state.

CPUA Decommissioned

CPU A transitioned from the commissioned
state to the decommissioned state.

Contact GE Post Sales Service if this occurs
when not expected (see

How to contact us

on page 2

).

CPUB Decommissioned

CPU B transitioned from the commissioned
state to the decommissioned state.

Contact GE Post Sales Service if this occurs
when not expected (see

How to contact us

on page 2

).

Command and Control Power Related

Breaker Close Command Issued
from HMI For [Breaker Name]

Logged when an operator issues a close
command for a given breaker

Breaker Open Command Issued
from HMI For [Breaker Name]

Logged when an operator issues an open
command for the specified breaker

Breaker Trip Command Issued
from HMI For [Breaker Name]

Logged when an operator issues a trip
command for the specified breaker

[Alarm Name] Is In Alarm
Condition

The specified alarm has entered the active
condition.

Attention: Control Power 1
Outage Detected On Battery
Backup

The primary control power source has
experienced an outage and is now operating
from the UPS battery backup.

Attention: Control Power 1 Low
Battery Detected Shutdown in 2
mins

The HMI will shutdown in the specified
amount of time due to impending outage of
the UPS battery backup.

Control Power 1 Power Restored Power has been restored to the primary

control power bus.

<USER ID> Requested Multipoint
RELT

Logged by HMI when user initiates RELT

<USER ID> Requested To End
Multipoint RELT

Logged by HMI when user turns off RELT

CPU-Related Events

These events are generated within the CPU
and retrieved by the HMI via
communications.

Relays – Voltage

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips