Overcurrent protection

61

5

Entellisys limits the maximum Instantaneous Overcurrent Pickup Setting (P

IOC

) Multiplier based

on frame type and whether or not Short Time protection is enabled. This relationship is shown
for EntelliGuard circuit breakers in Table 5-3 below:

Parameters such as IOC pickup, ST pickup, curve type and delay bands for Short Time protection
are set in the HMI, as shown in Figure 5-2.

Figure 5-2 Setting parameters of IOC/ST protection for Breaker 2

Table 5-3 Maximum P

IOC

Breaker Frame
Size

Maximum P

IOC

with

Short Time

Maximum P

IOC

without

Short Time

800

15

10

1600

15

10

2000

15

10

3200

13

10

4000

9

9

5000

7

7