GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 261

Advertising
background image

Alarms and events description and system troubleshooting guide

261

A

Time Synchronization
Successful

When in client mode CPU logs this event
when it received the time packet from time
server for the first time.

Time Server Not Responding Or
Not Reachable

When in client mode CPU logs this event
when there was no response from time
server for time packet request.

Time Server Not Configured

Logged when server IP address has default
value of 0.0.0.0

Breaker Tripped Analog IOC

Messenger reports that it has tripped the
breaker due to an IOC condition (analog
circuit)

Breaker Trip Instantaneous
Overcurrent

Messenger reports that it has tripped the
breaker due to an IOC condition

Breaker Trip Backup ST
Overcurrent

Messenger reports that it has tripped the
breaker due to a short time overcurrent
condition

Breaker Trip Backup LT
Overcurrent

Messenger reports that it has tripped the
breaker due to a long time overcurrent
condition

Breaker Trip Backup Ground
Fault

Messenger reports that it has tripped the
breaker due to a ground fault condition

Caution CPUA Not Rcv From 1 Or
More Messngrs

Messenger reports that CPU A is not receiving
data from at least one Messenger (event
recorded by CPU B)

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU A.
Verify that Messenger is powered on and
operating.

Caution CPUB Not Rcv From 1
Or More Messngrs

Messenger reports that CPU B is not receiving
data from at least one Messenger (event
recorded by CPU A)

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that Messenger is powered on and
operating.

Caution Messngr Not Receiving
From CPUA

Messenger reports that it is not receiving
data from CPU A

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU A.
Verify that CPU A is powered on and
operating.

Caution Messngr Not Receiving
From CPUB

Messenger reports that it is not receiving
data from CPU B

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that CPU B is powered on and
operating.

System OK Receiving Broadcast
From CPUA

Messenger reports that it is receiving data
from CPU A

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips