GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 244

Advertising
background image

Alarms and events

244

A

Clock and Time Synchronization Related

Time Synchronization Disabled

Logged to record that the HMI is no longer
synchronizing the real-time clock on each
CPU

Time Synchronization Enabled

Logged to record that the HMI is now
synchronizing the real-time clock on each
CPU

Time Synchronization
Frequency Set To [NN] Hours

Logged to record a change in the setting
which determines how often the HMI
synchronizes the real-time clock on each CPU

Time Synchronization
Successful

Logged each time the HMI synchronizes the
real-time clock on each CPU

Caution: Time Synchronization
Failed with [CPU A/B]

Logged when the HMI is unable to
synchronize the real-time clock of a given
CPU

See the communications troubleshooting tips
above (

Troubleshooting communications

between an HMI and a CPU: on page 241

).

Caution: Daylight Savings Time
Error X

The HMI was unable to resolve the time zone
settings

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Daylight Savings Time in Effect,
Time Synchronized

Logged when a daylight savings transition
and resynchronization occurs

Standard Time in Effect, Time
Synchronized

Logged when a return to standard time and
resynchronization occurs

Time Synchronization
Successful

Logged the first time or first time since last
failure when HMI time sychronization is
successful

Time Server Not Responding Or
Not Reachable

Logged once if time synch fails

See chapter 5.5 in DEH-430 the System
Administrator’s manual for troubleshooting

Unable to start Windows Time
Service. Time Synchronization
Failed

Logged by HMI on startup if it is not able to
start the Windows Time Service during
initialization of the time service routines. This
impacts only HMI synchronization, CPUs may
be correctly synchronized.

May be due to the operating system
permissions on the HMI. Login to the
computer as an administrator, navigate to
the time sync screen and toggle the Sync
HMI checkbox. See chapter 5.5 in DEH-430
the System Administrator’s manual for
troubleshooting

Caution: Unable to stop
Windows Time Service

Logged by HMI on shutdown if it is not able to
stop the Windows Time Service. Attempt to
stop Time service is performed only if it was
not running previously before starting HMI

CPU Settings Related

Default CPU set to CPUA

The default view for the HMI has been set to
CPU A

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips