External device setup manual – IDEC High Performance Series User Manual

Page 124

Advertising
background image

Chapter 2

106

External Device Setup Manual

Word Device

Device Name

Device Symbol

Address Range

Read
/Write

Address
Gradual

MICRO/I

PLC

Input Relay

WX

X

0 - 1F0

R

*1

*2

*1. Set this device using hexadecimal.
*2. Set this device using a multiplier of 16.

Output Relay

WY

Y

0 - 1F0

R/W

*1

*2

Internal Relay

WM

M

0 - 2032

R/W

*2

Link Relay

WB

B

0 - 3F0

R/W

*1

*2

Latch Relay

WL

L

0 - 2032

R/W

*2

Timer (current value)

TN

T

0 - 255

R

Counter (current value)

CN

C

0 - 255

R

Data Register

D

D

0 - 1023

R/W

Link Register

W

W

0 - 3FF

R/W

*1

Annunciator

WF

F

0 - 240

R/W

*2

Special Internal Relay

WSM

SM

9000 - 9240

R

*3

*3. This can only be used when the Link Unit is being used.

Special Register

SD

SD

9000 - 9255

R

File Register

R

R

0 - 8191

R/W

- File Register is not available, if Memory Cassettes is used.

- File Register is tested only MELSEC-A1S/A1SH/A1SJH/A2SH/A2C.

Don’t use expect those CPU Unit.

- In case of using File Register, must reset to MICRO/I if PLC parameter is changed.

Advertising