External device setup manual – IDEC High Performance Series User Manual

Page 208

Advertising
background image

Chapter 2

190

External Device Setup Manual

4.4.4

Ethernet/IP (ControlLogix, CompactLogix, PLC-5, SLC 500, MicroLogix)

4.4.5

ControlLogix, CompactLogix, FlexLogix

Communication Interface Setting (Ethernet)

Item

Setting

Interface

Ethernet

IP Address

Set the IP address of MICRO/I.

Subnet Mask

Set the subnet mask of MICRO/I.

Default Gateway

Set the default gateway of MICRO/I.

Host I/F Network Setting
Set some network information of PLCs. It can be set to maximum of 16.

Item

Setting

Station No.

The number to select PLC when set device address.

IP Address

Set the IP address of communicated PLC.

Port Number

Set the port number of communicated PLC.

Product

Set the product of communicated PLC.

(For ControlLogix or CompactLogix, select «Logix».)

Slot Number

Set the CPU slot number of communicated PLC.

Item

Setting

Baud Rate (bps)

*1

*1. The setting for this item must match the setting on the MICRO/I Series unit.

1200, 2400, 4800, 9600 or 19200

Data Bits

*1

8 (fixed)

Parity

*1

None or Even

Stop Bits

*1

1

Flow Control

None

Serial Interface

RS232C

Protocol

DF1 Point to Point

*2

*2. Be certain to select as indicated.

Control Line

No Handshaking

*2

Error Detection

BCC or CRC

Embedded Response

Auto Detect

Duplicate Packet Detect

Enable

Station Address

*1

*3

*3.Select the MICRO/I Node Address using the Station Address (MICRO/I) under Configuration - System Setup - Project -

Host I/F Driver in WindO/I-NV2.

0 to 254 (decimal)