10 error codes, 1 response time, Response time – IDEC High Performance Series User Manual

Page 614: External device setup manual

Advertising
background image

Chapter 4

596

External Device Setup Manual

10 Error Codes

When a command that starts with the ENQ (05h) code and ends with CR (0Dh) code is received, but the content is
not valid, an error response is returned.

The error response codes are as follows.

The error code is a code appended to a negative acknowledgment when DM LINK(1:N) or DM LINK(1:1) is set in Host
I/F Driver and 1 is selected in Protocol. Not used when 0 is selected in DM LINK(1:1).

10.1 Response Time

The MICRO/I or Touch replies to commands from the external device within 10msec plus the transmission wait.

Error Code

Type

Error Description

'2' (32h)

BCC

BCC doesn't match (when “with BCC” is set)

'3' (33h)

Command

A command other than 'W' or 'R' was received

(with the exception of the Clear command)

'4' (34h)

Address

Invalid DM address (other than DM0 to DM8191)

'5' (35h)

No. of Words

Invalid number of words specified
(outside the range 1 to 255 or the DM address + No. of words - 1 exceeds 8191)

'6' (36h)

Received Bytes

Received bytes invalid (the number of words of data did not exist)

Advertising
This manual is related to the following products: