Chapter 2

512

External Device Setup Manual

20.4 Environment Settings

Refer to the followings to configure the communication port between PLC (PROSEC T Series or V Series) and MICRO/I.
Attend to the limitation of the configuration. It depends on the CPU unit and Link unit.

20.4.1

LG Industrial Systems MASTER-K K10S1, K80S, K120S, K200S (Loader Port)

20.4.2

LG Industrial Systems MASTER-K K80S, K200S, K300S (Interface Module)

Refer to the MASTER-K Series user’s manual for details of communication settings.

Items

Details

Interface

RS232C

Baud Rate [bps]

38400

Data Bits

8

Parity

None

Stop Bits

1

Flow Control

None

Items

Details

Interface

RS232C, RS485 4-wire

Baud Rate [bps]

1200, 2400, 4800, 9600, 19200 or 38400

Data Bits

7 or 8

Parity

None, Odd or Even

Stop Bits

1 or 2

Flow Control

None or Hardware

Station No.

00 - 1F(HEX)