Chapter 2

150

External Device Setup Manual

3.4

Environment Settings

3.4.1

PLC Link Unit Settings

Perform the settings using the rotary switches and DIP switches on the Link Unit.

Item

Setting

Interface

RS232C

RS485

Transmission Control Protocol

1:N

Command Level

Levels 1, 2 and 3 are valid

Baud Rate

Use the same

settings as for the

MICRO/I.

1200, 2400, 4800, 9600 or 19200

Transmission Code

7 or 8 bit ASCII

Stop Bits

1 or 2

Unit No.

*1

*1. Set a decimal number for the Unit No.

0 to 31(DEC)

Parity

Even or Odd

CTS Switch

0V (always on)

Synchronization Switch

Internal

Termination Resistor

----------

Yes

- Refer to the Link Unit manual for details.

- Select using Register Command or not in Project Settings - Host I/F Driver.