Chapter 4

588

External Device Setup Manual

8

DM Link 1:N Communication Format

The communication format with DM Link 1:N Communication is as follows.

Command (Response)

Read

Write Clear

8.1

Read

The Read command is used by the external device to read the MICRO/I or Touch data memory.
One command can read a maximum of 255 words of data.

8.1.1

Command

Format

Detailed description

Command

Code

Description

Bytes

ENQ

05h

Command Start

1

Station Number

DM Link Station Number expressed in ASCII.

2

R

52h

Read Command

1

DM address

DM address to start reading from

This is expressed as the ASCII code of the hexadecimal value of the address.

4

Words

Number of words to read

The hexadecimal value expressed using ASCII code.

2

BCC

Only required when 'with BCC' is set.

Exclusive OR (HEX) from ENQ to before BCC converted to ASCII code.

2

CR

0Dh

End

1