External Device Setup Manual

5.4.2

S7-300/400 with Communication Module

The communication port settings for S7-300 and MICRO/I host port are as follows.

5.4.3

S7- 300 with MPI Interface

The communication port settings for S7-300 and MICRO/I host port are as follows.

Items

Details

Interface

Use the same settings as for the
MICRO/I.

RS232C

Baud Rate (bps)

1200, 2400, 4800, 9600, 19200 or 38400

Data Bits

8 (Fixed)

Parity

Even, Odd or None

Stop Bits

1 or 2

BCC

Enable or Disable

Priority

Low

- MICRO/I type performs communication based on 3964 (R) and RK512 protocol.

- CP340 is supporting only the 3964 and 3964R protocol. Therefore when using CP340, it is necessary to construct the pro-

gram to realize RK512 protocol in PLC. This is programmed using the function blocks FB2 and FB3, in SIEMENS PLC.

- CP341 is supporting 3964 (R) and RK512 protocol, please choose RK512 by setup PLC.

- The program of CP340 refers to a sample program.

The sample program is recorded on CD-ROM after Wind O/I NV2 Ver2.50.
Please refer to the following folder.
(Wind O/I NV2 CD-ROM) /Sample/Host_if/SIEMENS/ Downloading from our Web site is possible.

Items

Details

Interface

Use the same settings as for the MICRO/I.

RS422/485 2-wire

Baud Rate (bps)

19200 or 187500

Data Bits

8 (Fixed)

Parity

Even (Fixed)

Stop Bits

1 (Fixed)

HG Node Address

It should not be duplicated to other node addresses

1 - 126 (The default value is 1)

PLC Node Address

Use the same settings as for the MICRO/I.

1 - 126 (The default value is 2)

Maximum MPI Address

1 - 126 (The default value is 31)