External Device Setup Manual

3.4.4

C200H

(Communication Board) Settings

Write the Communication Board setting items for the System Settings Area using a peripheral tool (such as Proconn).

Set DIP switch SW1 to the 4 side (4 lines).

Set DIP switch SW2 to ON to turn the termination resistor setting ON. Refer to the Communication Board manual for
details.

System Settings Area

Item

Setting

Port A

Port B

DM6555

DM6550

Standard Setting/Individual Setting

*1

*1. Standard settings

Baud Rate: 9600bps
Data Bits: 7 bits
Stop Bits: 2 bits
Parity: Even

Same setting as the MICRO/I.

Mode

PLC Link Mode

DM6556

DM6551

Communication parameters for when the
previous item is set to Individual.

Same setting as the MICRO/I.

DM6557

DM6552

Transmission Delay

0 msec

DM6558

DM6553

Unit No.

Same setting as the MICRO/I.