5.4

Environment Settings

5.4.1

S7-200

The communication port settings for S7-200 and MICRO/I host port are as follows.

Items

Details

PLC Address

1 to 126(Dec) (0 to 7e (Hex))

Set the value to same value as ADDRESS (PLC) in WindO/I-NV2.

Highest Address (Highest Station
Address)

1 to 126(Dec) (0 to 7e(Hex))
Set the value to same value as HSA in WindO/I-NV2.

Baud Rate (bps)

9600 or 19200
Set the value to same value as Baud Rate in WindO/I-NV2.

HG Address

0 to 7e (Hex) (0 to 126(Dec))
Set the value as ADDRESS (HG) in WindO/I-NV2.

Data Bits

8 (fixed)
Set the value in WindO/I-NV2.

Parity

EVEN (fixed)
Set the value in WindO/I-NV2.

Stop Bits

1 (fixed)
Set the value in WindO/I-NV2.

- Set the communication port that communicates with MICRO/I to PPI/Slave mode. Please make sure to set SMB30 or

SMB130 values to 0 in order to select proper communication port settings. Refer to the manual of S7-200 for details.

- We checked the following problems in some versions of S7-200.

When S7-200 is set as the master and the address of S7-200 is the same as HSA, token path does not work correctly.
This problem can be solved by setting HSA as a larger value than Address actually used.
This problem does not occur when one MICRO/I is connected to one S7-200 PLC.