Event Transmission

This is used to perform Event Transmission when a value in the MICRO/I or Touch data memory is changed

7.5.1

Command

Format

7.5.2

Event Data Transmission Sequence

Detailed description

Command

Code

Description

Bytes

STX

02h

Command start

1

E

45h

Event Transmission command

1

DM Address

Event Transmission address. This is expressed as the ASCII code of the hexadeci-
mal value of the address.

4

Words

Event Transmission words. The hexadecimal value expressed using ASCII code.

2

Data

DM Address data.
The hexadecimal value expressed using ASCII code.

4

ETX

03h

Only required when “with BCC” is set.
Command end of the event transmission data.

1

BCC

Only required when 'with BCC' is set.
Exclusive OR (HEX) from ENQ to before BCC converted to ASCII code.

2

CR

0Dh

End

1

- Number of Event Transmission words should not be larger than the number of Max Event Transmission Words. If Max

Event Transmission Words is 0, then Event Transmission words is set to 1.

- The Max Event Transmission Words setting is set from 0 to 255.