External device setup manual – IDEC High Performance Series User Manual

Page 170

Advertising
background image

Chapter 2

152

External Device Setup Manual

3.4.3

CPU Unit RS232C Link I/F Settings (SYSMAC-CS1 Series)

Write the RS232C I/F setting items for the System Settings Area using a peripheral tool (such as Proconn).

Refer to the PLC manual for details.

For the SYSMAC-CS1 Series, set switch number 5 on the CPU Unit setting switch to OFF to enable you to make your own
communication settings.

Channel

Item

Setting

160

Optional/Initial Setting

*1

*1. Initial settings

Baud Rate: 9600 bps
Data Bits: 7 bits
Stop Bits: 2 bits
Parity: Even

Set to 1 for Optional Setting.

Serial Communication mode

Set to PLC Link.

Data Bits

Use the same settings as for the MICRO/I.

Stop Bits

Parity

161

Port Communication Speed

Use the same settings as for the MICRO/I.

162

In the case of No Protocol Mode

Do not set.

163

Unit No.

Set to the same as the MICRO/I PLC Link Station Number.

164

In the case of No Protocol Mode

Do not set.