External device setup manual – IDEC High Performance Series User Manual

Page 230

Advertising
background image

Chapter 2

212

External Device Setup Manual

4.6

The way to set device address when use ControlLogix, CompactLogix series

In ControlLogix and CompactLogix series, device is set with tag name. However, you have to set with a Symbol and Address format
that is the same as MicroLogix, SLC 500 and PLC-5 because WindO/I-NV2 can not operate a tag name directly.

You have to attach each tag name to a device symbol and device address at that time.

This is called mapping.

4.6.1

The way of mapping

The following work is done in RS Logix 5000 software.

1. Define some tags to communicate with MICRO/I in “Controller Tags”

2. Select “Logic” and “Map PLC/SLC Messages…” on main menu in RS Logix 5000 software.

3. Attach File Number to each tag name in “PLC3,5/SLC Mapping” dialog box.

4.6.2

The way to select device address in WindO/I-NV2

When select device address in WindO/I-NV2, set tag type to device symbol and set array number to File Number.

4.6.3

The process to select device address

Set device address in WindO/I-NV2 software.

Define some tags in RSLogix 5000 software.

Tag name

Data Type

Array

Tag_A

INT

[10]

Tag_B

SINT

*1

*1. Must define SINT type’s tag with couple of byte.

[10]

Tag_C

DINT

[10]

Tag_D

REAL

[10]

Do mapping tag to File Number.

Tag name

Data Type

Array

File Number

Tag_A

INT

-

1

Tag_B

SINT

[10]

-

2

Tag_C

DINT

[10]

-

3

Tag_D

REAL

[10]

-

4