External Device Setup Manual

1.6.2

System Configuration

The following is the system configuration.

1.6.3

Wiring

Make sure to use commercially available 10BASE-T ready cables for connecting the devices.

Use a straight cable when using a hub, and use a crossing cable when directly connecting to the MICRO/I or Touch and an external
device.

1.6.4

Devices

The following devices are available for Modbus TCP Server communication.

All devices are general-purpose devices intended for nonspecific purposes.

- Up to 4 external devices can communicate with a single MICRO/I or Touch unit at one time.

- The MICRO/I or Touch unit and an external device can be directly connected on a 1:1 basis by bypassing a hub. In this

case, use a crossing cable for the connection.

Bit Device

Device Name

Device
Symbol

Address Range

MICRO/I or
Touch
Read/Write

External
Device
Read/Write

Address
Gradual

HG2G-S/-5S/-5F,
HG3G/4G, Touch

HG1F/2F/2S/3F/4F

Coil Status

C

1 - 4096

1 - 65536

R/W

R/W

Decimal

Input Status

I

100001 - 104096

100001 - 165536

R/W

R

Decimal

Word Device

Device Name

Device
Symbol

Address Range

MICRO/I or
Touch
Read/Write

External
Device
Read/Write

Address
Gradual

HG2G-S/-5S/-5F,
HG3G/4G, Touch

HG1F/2F/2S/3F/4F

Holding Register

HR

400001 - 404096

400001 - 465536

R/W

R/W

Decimal

Input Register

IR

300001 - 304096

300001 - 365536

R/W

R

Decimal