External Device Setup Manual

1.6.6

Communication Format

This chapter describes the communication format of the Modbus TCP Server communication.

The Modbus TCP Server communication supports Class 0 and Class 1 functions of the OPEN Modbus TCP SPECIFICATION
Release1.0. For details about the communication methods, refer to the OPEN Modbus TCP SPECIFICATION Release1.0 as well as
this manual.

1. Preparations for Communication

The Modbus TCP Server performs communications using the TCP. Make sure to establish a connection with the specified port of the MICRO/I or
Touch with TCP before executing reading/writing of devices.

2. Basic Format

The following table lists the basic format of communications. The same format applies to both requests and responses.
Data is processed as a byte sequences.

3. Reference Numbers

Reference numbers are used to specify a device address with the Modbus TCP.

The reference number is obtained by subtracting 1 from the 1st to 5th value of the device address, and is expressed in hexadecimal format.

The following table lists the address of each device and the corresponding reference number.

Byte

Description

Byte 0

Transaction ID

*1

. The same value is returned from the server. The value is normally “0”.

*1. The data included in a request is returned from the server without changes. The client (external device) sends a different Transaction ID for

each request, and identifies the response by checking the Transaction ID of a response. Enter “0” to not check the Transaction ID.

Byte 1

Transaction ID

*1

. The same value is returned from the server. The value is normally “0”.

Byte 2

Protocol ID

*2

. The value is always “0”.

*2. The number indicating the Modbus TCP protocol, and is always “0”.

Byte 3

Protocol ID

*2

. The value is always “0”.

Byte 4

Message length

*3

(high byte). The value is always “0”. (Since the message is 256 bytes at maxi-

mum.)

*3. Indicates the length of the following message in units of bytes.

Byte 5

Message length

*3

(low byte). The length of the following message.

Byte 6

Unit ID

*4

*4. ID used for identifying devices. The ID is not used with the MICRO/I or Touch. When the ID is used in a request, the returned data is

unchanged.

Byte 7

Function code

*5

*5. Numbers assigned for functions such as reading and writing.

Byte 8-

Data

*6

*6. Data required for each processing.

Address

Reference
No.

Address

Reference
No.

Address

Reference
No.

Address

Reference
No.

C 1

0001

I 100001

0001

HR 400001

0001

IR 300001

0001

C 2

0002

I 100002

0002

HR 400002

0002

IR 300002

0002

C 65535

FFFE

I 165535

FFFE

HR 465535

FFFE

IR 365535

FFFE

C 65536

FFFF

I 165536

FFFF

HR 465536

FFFF

IR 365536

FFFF