7 process monitor operation, 8 hazard/tornado condition operation – Fire-Lite MS-10UD Series FACP User Manual

Page 100

Advertising
background image

100

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Operating Instructions

Process Monitor Operation

Communicate the supervisory condition to the Central Station

The supervisory relay is activated

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Terminate upload or download communications

A typical Supervisory event would be displayed as illustrated in the following:

In the preceding example:

FROZEN SUPRV - indicates zone detector is below approximately 45

o

F

Note that, like alarms, supervisory signals latch, except when programmed for supervisory autore-
settable. Supervisory activations do not cause silenced alarms to resound, as do other alarm condi-
tions. Open circuits in supervisory wiring are processed by the control panel the same way as other
trouble conditions. Refer to “Alarm Operation” on page 99, for a description of the information
displayed on the control panel LCD.

4.7 Process Monitor Operation

Process Monitor operation will initiate the following events:

The piezo sounder pulses ¼ second On and ¼ second Off

The LCD displays a process monitor message along with the device name, type,
adjective/noun, associated zones and time/date

Communicate the process monitor condition to the Central Station (if the default event code
has been changed from 000 to a reportable event code)

Relays programmed for process monitoring will be activated

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.

4.8 Hazard/Tornado Condition Operation

Hazard/Tornado operation is intended for Manual activation.

Hazard/Tornado Condition operation will initiate the following events:

The piezo sounder pulses ¼ second On, ¼ second Off

The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date

Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)

Relays programmed for hazard will be activated

FREEZE SUPERVISORY

<ADJ> <NOUN>

ZONE 05 FROZEN SUPRV

10:00A 100913