MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

69

Master Programming Level

Programming

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 2 while viewing NAC Screen #2. The following
screens will be displayed:

To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #1.

Silence Inhibited

The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board
NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while
the NAC programmed for silence inhibit is activated. Pressing 3 while viewing NAC Screen #2
will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence
Inhibit.
Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute
Silence Inhibit for the selected Output.

3.5.3 Relays

Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:

To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screens will appear for each relay to be programmed:

While viewing the selected screen, press the number corresponding to the desired relay type to pro-
gram the main circuit board relay. The choice will be stored in memory and the display will return
to the Relay Type Screen which will show the programmed type choice. Press the Escape key to
return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.

3.5.4 System Setup

System Setup allows the programmer to configure the following control panel features:

Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay

PROGRAM NAC #

1=SILENCEABLE YES

2=AUTO SILENCE NO

3=SIL INHIBITED NO

NAC Screen #2

AUTO SILENCE

1=NO

2=5 MINUTES

3=10 MINUTES

Auto Silence Screen #1

AUTO SILENCE

1=30 MINUTES

Auto Silence Screen #2

AUTO SILENCE

1=15 MINUTES

2=20 MINUTES

3=25 MINUTES

Auto Silence Screen #3

PROGRAMMING

1=INPUT ZONES

2=NACS

3=RELAYS

Programming Screen #1

RELAYS

1=RELAY 1 ALARM

2=RELAY 2 TROUBLE

3=RELAY 3 SUPERV

Relays Selection Screen

RELAY TYPE

1=ALARM

2=TROUBLE

3=SUPERVISORY

Relay Screen #1

RELAY TYPE

1=PROCESS MONITOR

2=AC LOSS

3=HAZARD

Relay Screen #3

RELAY TYPE

1=COMM FAIL

2=MEDICAL

3=SILENCEABLE ALARM

Relay Screen #2

NOTE: A relay programmed with the Silenceable Alarm type will deactivate when the FACP
Alarm Silenced LED is illuminated.