Medical Alert Condition Operation

Operating Instructions

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Hazard conditions latch.

4.9 Medical Alert Condition Operation

Medical alert operation is:

not intended for nurse call stations (applications) per UL1069.

not intended for signaling professional medical staff.

to be used for summoning security guards or other trained personnel within the facility

intended for Manual activation.

Medical Alert Condition operation will initiate the following events:

The piezo sounder ¼ second On, ¼ second Off

The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date

Communicate the medical alert condition to the Central Station (if the default event code has
been changed from 000 to a reportable event code)

Relays programmed for medical alert will be activated

The alarm relay is not activated

Silenced alarms are not resounded

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Medical alert conditions latch.

4.10 Disable/Enable Operation

Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. All disabled zones/NACs are treated as if they were in trouble, with the excep-
tion being the status label that will be displayed is DISABL.

4.11 Waterflow Circuits Operation

If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.