3 ann-sec option card, Ann-sec option card – Fire-Lite MS-10UD Series FACP User Manual

Page 40

Advertising
background image

40

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Installation

Installation of Optional Modules

Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):

Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building

Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:

Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building

Before installing the module, place the disconnect switch to the down (disconnect) position to pre-
vent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after
the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate
the Disconnect condition.

2.7.3 ANN-SEC Option Card

The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.

1.

Remove the chassis mounting screw to the right of TB3 and replace it with the supplied 0.5” x
4-40 male-female standoff.

2.

Install the header into J13 on the main circuit board.

Figure 2.17 4XTMF Transmitter Module

Connect to FACP Connectors J4 & J5

Disconnect
Switch
shown in
disconnect
position

TBL Jumper

Remote Alarm - Class 2

(power-limited)*

Remote Trouble - Class 2

(power-limited)*

No connection

Municipal Box (nonpower-limited)*

1+
2-
3+
4-
5
6+
7-

Polarities are shown for module activation

Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal.
For an application of reverse polarity of a supervisory signal, refer to the Appendix titled “FACP with
Keltron” on page 131
.

* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7K

, ¼ watt resistor) if

Municipal Box is not connected.

Disconnect LED

4

x

tm

f.

w

m

f