Appendix F: Canadian Application

F.1 ANN-LED Annunciator Installation for Canadian

Applications

The FACP is supplied with a modified dress panel and one ANN-LED annunciator.

When installing and programming the FACP, the Canadian Option must be set to ON prior to
any other panel programming (refer to “Canadian Option” on page 74 of the Programming
Section of this manual).

If remote indicators are desired, they must be connected to the secondary ANN-BUS circuit.
This requires the use of the ANN-SEC option card.

The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door.

To comply with CAN/ULC-S559-04, the ANN-RLY option must be utilized along with the
configuration shown in Figure F.2.

Figure F.1 Canadian FACP Configuration

FACP

ANN-LED Annunciator
on Primary ANN-BUS

51

0

-an

nl

ed

.w

mf

ANN-LED

ANN-80C

ANN-I/O

ANN-S/PG

ANN-RLY

Optional Secondary

ANN-BUS using

ANN-SEC Option Card.