Master Programming Level

Programming

Erase History

The Erase History option allows a user to erase all events from the history file. This will provide a
clean slate in order to use the history file to track future events. Pressing 2 while viewing the His-
tory Screen will display the following screen:

Pressing 1 while viewing the Erase History Screen will erase all events from the History file. After
the History file has been erased, the display will return to the History Screen.

3.5.7 Walktest

Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Refer to the sections titled “Walktest” on page 94 and“Walktest”
on page 104 fo
r additional information regarding the Walktest feature. Pressing 1 while viewing
the Programming Screen #3 will cause the following Walktest options to be displayed:

To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the follow-
ing screen will be displayed:

The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the walk-
test screen from an actual alarm screen.

After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:

Use the up and down arrow keys to view all of the walktest results which will be displayed as illus-
trated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and
DC) is removed from the FACP, the Walktest log information will be lost. This information is also
overwritten when subsequent walktests are performed.

ERASE HISTORY

PROCEED?

1=YES 2=NO

Erase History Screen

PROGRAMMING

1=WALKTEST

2=CLEAR PROGRAM

3=PASSWORD CHANGE

Programming Screen #3

WALKTEST

1=SILENT

2=AUDIBLE

3=VIEW RESULT

Walktest Screen

UNIT IN WALKTEST

Walktest Active Screen

ALARM ZONE 1

<ADJ> <NOUN>

Z01

1000A 010805

WALKTEST RESULTS