6 maintenance programming level, 1 input zones - enable/disable, Maintenance programming level – Fire-Lite MS-10UD Series FACP User Manual

Page 93: Input zones - enable/disable

Advertising
background image

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

93

Maintenance Programming Level

Programming

The following screen will appear when one of the change options is selected:

A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:

The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.

3.6 Maintenance Programming Level

To access Maintenance Programming mode, press the Enter key. The LCD will display the follow-
ing:

To enter the Maintenance Programming mode, press 2. The display will read as follows:

When the Maintenance level password (default 11111) is entered, the following screen will appear:

Note that in the preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.

3.6.1 Input Zones - Enable/Disable

The Zone Setup option allows the user to enable or disable desired zones. Pressing 1 for Zone
Setup, while viewing Maintenance Screen #1 will cause the following screens to be displayed:

ENTER NEW FIVE DIGIT

PASSWORD

Enter Password Screen

VERIFY NEW

PASSWORD

Password Change Screen

1=READ STATUS

2=PROGRAMMING

3=REMOTE DOWNLOAD

PROGRAMMING

ENTER PASSWORD

PROGRAMMING

1=INPUT ZONES

2=HISTORY

3=WALKTEST

PROGRAMMING

1=TIME-DATE

PROGRAMMING

1=INPUT ZONES

2=HISTORY

3=WALKTEST

Maintenance Screen #1

POINT PROGRAM

1=ZONE 1

2=ZONE 2

3=ZONE 3

Zone Select Screen