Fire-Lite MS-10UD Series FACP User Manual

Page 85

Advertising
background image

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

85

Master Programming Level

Programming

Ademco Contact ID Format - Secondary Central Station Phone Number

The information shown in Table 3.5 is automatically programmed for the Secondary Central Sta-
tion phone number Event Codes when Ademco Contact ID Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to dis-
able it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).

Event Description

Event Code Settings

Active

Secondary # Zone 1 - 10 Alarm

115

Secondary # Zone 1 - 10 Disabled

570

Secondary # Drill

604

Secondary # AC Fault

301

Secondary # Zone 1 - 10 Fault

380

Secondary # Zone 1 - 10 Dirty

380

Secondary # Earth Fault

310

Secondary # Low Battery Fault

302

Secondary # No Battery Fault

311

Secondary # Telco Primary Line Fault

351

Secondary # Telco Secondary Line Fault

352

Secondary # NAC #1 Fault

321

Secondary # NAC #2 Fault

322

Secondary # NAC #3 Fault

326

Secondary # NAC #4 Fault

327

Secondary # NAC #1 Disable

521

Secondary # NAC #2 Disable

522

Secondary # NAC #3 Disable

526

Secondary # NAC #4 Disable

527

Secondary # Charger Fault

300

Secondary # Comm Trouble Primary #

354

Secondary # Comm Trouble Secondary #

354

Secondary # Printer Fault

336

Secondary # ANN-BUS Fault

330

Secondary # Option Card Fault

333

Secondary # CS CALC Fault

304

Secondary # System Off Normal

308

Secondary # System Test Message

602

Secondary # System Abnormal Test Message

608

Secondary # Upload/Download Request

411

Secondary # Upload Successful

416

Secondary # Download Successful

412

Secondary # Upload/Download Failed

413

Secondary # Voice EVAC Fault

330

Secondary # Power Supply Sync fault

300

Table 3.5 Ademco Contact ID Secondary # Event Codes