Fire-Lite MS-10UD Series FACP User Manual

Page 137

Advertising
background image

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

137

ANN-LED Annunciator Installation for Canadian Applications

Canadian Application

Notes:

1.

Relays 1 and 2 on the ANN-RLY must be programmed for latching alarm activation.

2.

Relays 3 and 4 on the ANN-RLY must be programmed for non-latching trouble activation.

3.

Relays 5 and 6 on the ANN-RLY must be programmed for supervisory activation with
latching/non-latching set in accordance with the local AHJ.

4.

The ANN-RLY must be mounted inside the FACP cabinet.

5.

Refer to the ANN-RLY Document #53033 for installation instructions.

Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals

FACP

ANN-RLY

+

ALARM

-

+

TROUBLE

-

+

SUPERVISORY

-

C
NC
NO

C
NC
NO

C
NC
NO

C
NC
NO

C
NC
NO

C
NC
NO

Relay 1
TB2

Relay 2
TB2

Relay 4
TB4

Relay 6
TB5

Relay 3
TB4

Relay 5
TB5

To Remote Station Receiver

TB9

Non-resettable
Aux Power

2
1

-

+