A.1 transmission format between dact and receiver, A.2 ademco contact id typical printout – Fire-Lite MS-10UD Series FACP User Manual

Page 120

Advertising
background image

120

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Appendix A: Ademco Contact ID Format Event Code

Descriptions

This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.

A.1 Transmission Format Between DACT and Receiver

The transmission string for the Ademco Contact ID Format is as follows:

SSSS 18 QXYZ GG CCC where

SSSS

= Four digit Subscriber ID Account Code

18

= Identifies transmission as Contact ID to the receiver at the Central Station

Q

= Event Qualifier where 1 = New Event and 3 = New Restore

XYZ

= Event code

GG

= Group number

CCC

= Zone number

Notes:

1.

18, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.

2.

GG Group Number is fixed at '00' and cannot be changed.

3.

CCC for Zone Number is transmitted as ‘001’ for zone 1 up to ‘010’ for zone 10

A.2 Ademco Contact ID Typical Printout

A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:

Notes:

1.

11 is an example of a Receiver/Line Card, showing which receiver and line card the message
was transmitted to.

2.

Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.

Time

Date

Rcvr/Line ID

SSSS

QXYZ

GG

CCCC

11:28

03/25

11

7777

E110

00

C001 - general fire alarm on zone one

11:28

03/25

11

7777

E111

00

C002 - smoke detector alarm on zone two

11:28

03/25

11

7777

E380

00

C003 - fault on zone three

11:28

03/25

11

7777

E570

00

C009 - Zone nine disabled

11:28

03/25

11

7777

R110

00

C001 - Zone one alarm restored

11:28

03/25

11

7777

R111

00

C002 - smoke detector zone two restored

11:28

03/25

11

7777

R380

00

C003 - zone three fault restored

11:28

03/25

11

7777

R570

00

C009 - zone nine reenabled

11:28

03/25

11

7777

E158

00

C006 - high temperature, zone six

11:28

03/25

11

7777

E151

00

C007 - gas detected, zone seven

Advertising