Programming

Master Programming Level

The following examples show the editing of Input Zone 1:

Enable/Disable Zone

To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each
press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is
selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms
and troubles to the panel. The control panel LCD will display the zone which has been disabled
and FACP will turn on the Trouble LED.

Type

To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:

Pressing the down arrow key will display additional zone types as indicated in the following table.

Some of the following Zone Types are not available for Canadian applications. Refer to “Canadian
Option” on page 74 fo
r additional details.

Zone Type

Action When Activated

Pull-Station

Fire Alarm

Waterflow

Fire Alarm Delayed (uses waterflow delay)

Waterflow Nonsilenceable

Fire Alarm (uses waterflow delay)

Combo

Fire/Supervisory (uses waterflow delay)

Combo AutoResettable

Fire/Supervisory AR, nonlatching (uses waterflow delay)

2-Wire Detector

Fire Alarm

Normally Open Contact

Fire Alarm

Fire

Fire Alarm

Tamper

Supervisory

Supervisory

Supervisory, latching

Supervisory AutoResettable

Supervisory, nonlatching

Medic-Alert Supervisory,

latching

Hazard-Alert

Supervisory, latching

Tornado-Alert

Supervisory, latching

Table 3.1 Zone Types

INPUT ZONE 1

1=ENABLED YES

2=TYPE PULL STATION

3=VERIFICATION NO

Edit Input Zone Screen #2

INPUT ZONE 1

1=PAS/PRE-SIG DELAY

NO DELAY

Edit Input Zone Screen #3

Edit Input Zone Screen #5

INPUT ZONE 1

1=ADJECTIVE/NOUN

2=DESCRIPTION


INPUT ZONE 1

1=FREEZE SUPV. NO

2=ACC MSG# 2

Edit Input Zone Screen #4

INPUT ZONE

1=ENABLED

2=TYPE

3=VERIFICATION

Edit Input Zone Screen #2

ZONE TYPE

1=PULL STATION

2=WATERFLOW

3=WATERFLOW NS

Zone Type Screen #1